Vapor Recovery Unit Maintenance: Best Practices and Troubleshooting

Why Maintenance Determines Recovery Performance

A 3-stage vapor recovery unit only delivers its rated efficiency when it is maintained. Dirty heat exchangers, leaking seals, and mis-calibrated sensors quietly reduce recovery performance while energy costs stay the same – or rise. A simple preventive maintenance program protects the investment and keeps the site compliant.

Daily and Weekly Checks

  • Visually inspect the unit for oil leaks, unusual vibration, or abnormal noise from the compressor and fans.
  • Check control panel alarms and log readings: inlet pressure, discharge temperature, and liquid level in the collector.
  • Verify that the vent stack is clear and that no liquid is pooling in vapor lines.
  • Record daily operating hours and recovered-liquid volume; a sudden drop signals a problem.

Monthly and Quarterly Tasks

  • Heat exchanger inspection: check for frost build-up, fouling, or blocked drain ports. Defrost and clean per the manufacturer’s instructions.
  • Compressor service: check oil level and condition, belt tension (if applicable), and discharge pressure.
  • Adsorption bed check: monitor bed pressure drop and regeneration cycle timing. Replace adsorbent at the recommended interval or when breakthrough is detected.
  • Membrane module care: for condensation-plus-membrane units, check inlet filters and membrane differential pressure; keep the feed clean to protect the membrane and maintain discharge NMHC levels.
  • Sensor calibration: verify pressure transmitters and temperature probes against known references.
  • Electrical inspection: confirm all explosion-protected enclosures are properly sealed and cable glands are tight.

Common Faults and How to Fix Them

SymptomLikely CauseAction
Recovery rate dropsFouled condenser, low refrigerant charge, or bypassing sealsClean coils; check refrigerant; inspect valves and gaskets
Excessive vibration / noiseLoose mounting, worn bearings, or unbalanced fanTighten mounts; replace bearings; balance or replace fan
Frequent cyclingIncorrect setpoints or leaking vapor-line valveReview control settings; repair or replace valve
High discharge odor / NMHC riseAdsorbent saturation, membrane damage, or fouled condenserRegenerate or replace adsorbent; inspect membrane module; clean condenser
Liquid carryover to stackBlocked demister or overfilled collectorClean demister; check level control and pump

Keep a Maintenance Log

Document every inspection, repair, and part replacement. A complete log proves due diligence to inspectors, helps predict spare-part needs, and makes troubleshooting faster when problems occur.

Service Support

Vohon provides commissioning support, operator training, and spare parts for its 3-stage vapor recovery units. Our service team can also audit an existing installation and recommend upgrades that restore or improve recovery performance.